Trip Class and Protection Features
Rated Trip Class 10, so it trips within 10 seconds at 7.2× the thermal setting — standard for protecting standard induction motors during startup. No ground fault detection on this variant, so if your application requires that, you'd need a separate ground-fault relay or a different SIRIUS model.
The 45 mm width and 75 mm depth fit standard panel layouts — it occupies one 45 mm slot on the rail, leaving room for auxiliary contact blocks or a downstream contactor in the same footprint. Clearance requirements: 20 mm above and below, 9 mm to the side, zero forwards or backwards — tight enough for dense panels if you respect the ventilation gaps.