Skip to main content
Siemens 3RV1011-0JA10-ZW96 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1011-0JA10-ZW96 SIRIUS Motor Protection CB, 100 k

MPN3RV1011-0JA10-ZW96
Active

Siemens SIRIUS 3RV1011-0JA10-ZW96, motor protection circuit breaker, 45 mm width, Trip Class 10, 100 kA interrupting capacity at 400 V, screw-type terminals, snap-on 35 mm DIN rail.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1011-0JA10-ZW96 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00

Electrical

3RV1011-0JA10-ZW96 — Electrical
ParameterValue
Rated operational current (Ie)1 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W

Protection & Tripping

3RV1011-0JA10-ZW96 — Protection & Tripping
ParameterValue
Overload release setting range0.7 ... 1 A
Instantaneous short-circuit trip current13 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V100 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV1011-0JA10-ZW96 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0

Connections

3RV1011-0JA10-ZW96 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)

Mechanical

3RV1011-0JA10-ZW96 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth75 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany

Environmental

3RV1011-0JA10-ZW96 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m

Specifications

3RV1011-0JA10-ZW96 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

What it is and what it does

The Siemens 3RV1011-0JA10-ZW96 is a SIRIUS motor protection circuit breaker designed to protect three-phase induction motors against overload and short circuit. Its Trip Class 10 means it trips within 10 seconds at 7.2× the thermal setting — fast enough to protect standard motors during a locked-rotor event without nuisance tripping on normal starts. The 100 kA interrupting capacity at 400 V (and at 690 V) means it can safely clear a bolted fault on a high-capacity distribution board without upstream fuses needing to coordinate down to a lower let-through.

Mounting and panel fit

Mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 60715. At 45 mm wide and 90 mm tall, it occupies a single module slot in a standard enclosure. The 75 mm depth leaves clearance for wiring behind the gland plate — no forced spacing needed. Screw-type terminals on the main circuit accept 2×(0.5–1.5 mm²) or 2×(0.75–2.5 mm²) solid or stranded copper, so it ties into existing panel wiring without terminal-block adapters. Mounting position is any, which simplifies layout in a crowded cabinet.

Frequently asked questions

Where can I buy 3RV1011-0JA10-ZW96 and how do I get a price?

This part is available to order against an RFQ through our independent distribution channel. Submit a request for a firm quote — availability and current pricing are confirmed at that time.

Will 3RV1011-0JA10-ZW96 drop into a panel that was specified around 3RV1011-0HA10 without rewiring?

Both are 45 mm wide SIRIUS motor protection breakers with the same screw-type terminal and snap-on DIN rail mounting. The 3RV1011-0HA10 carries a different current range, but the footprint and wiring interface are identical — no rewiring needed for the panel layout.

What is 3RV1011-0JA10-ZW96's listed depth (75 mm) on this component line?

The depth is 75 mm. That is the dimension from the DIN rail mounting surface to the front of the housing — standard for this SIRIUS frame size.

What is 3RV1011-0JA10-ZW96's listed width (45 mm) on this component line?

The width is 45 mm, which is the standard single-module width for SIRIUS 3RV1 breakers.

What compliance documentation does this brand provide for 3RV1011-0JA10-ZW96 (RoHS, REACH, UL, IEC)?

The SIRIUS series typically carries UL, CSA, CE, and IEC certifications, and the manufacturer publishes RoHS and REACH declarations. Specific document IDs for this exact order code should be confirmed at quote time.

MPN
3RV1011-0JA10-ZW96