Skip to main content
Siemens 3RV1011-0JA20 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1011-0JA20 SIRIUS Motor Protection Circuit Breake

MPN3RV1011-0JA20

Siemens SIRIUS motor protection circuit breaker, 3RV1011-0JA20, 1 A rated current, CLASS 10 trip class, 100 kA breaking capacity at 400 V AC, spring-loaded terminals, 45 mm width.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV1011-0JA20 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1011-0JA20 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W
3RV1011-0JA20 — Protection & Tripping
ParameterValue
Overload release setting range0.7 ... 1 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV1011-0JA20 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0
3RV1011-0JA20 — Connections
ParameterValue
Main-circuit terminal typespring-loaded terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.25 ... 1.5 mm²)
Conductor range, AWG (main contacts)2x (24 ... 14)
3RV1011-0JA20 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth81 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany
3RV1011-0JA20 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m
3RV1011-0JA20 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

The Siemens 3RV1011-0JA20 is a SIRIUS motor protection circuit breaker rated for 1 A continuous current with a CLASS 10 trip characteristic, sized for a 0.25 kW motor at 400 V AC. It delivers a 100 kA breaking capacity across the 240 V to 690 V range, so it can interrupt high fault currents without upstream fusing in most panel designs. The spring-loaded terminals on both main and auxiliary circuits accept 2x (0.25... 2.5 mm²) solid or 2x (0.25... 1.5 mm²) finely stranded with ferrule, which matches the wiring practice for control panels feeding motor starters.

IP20 finger-safe front protection allows panel-front access without additional shrouding. Any mounting position is permitted, which simplifies layout in crowded enclosures.

Protection and duty cycle

Rated for 15 operations per hour at AC-3 duty, which covers frequent starting cycles on conveyors or pumps. Power dissipation is 5.5 W total (1.8 W per pole) at rated load in hot operating state; account for this heat in enclosure sizing.

Frequently asked questions

What wire sizes do the spring-loaded terminals accept?

Main and auxiliary spring-loaded terminals accept 2x (0.25... 2.5 mm²) solid or 2x (0.25... 1.5 mm²) finely stranded with ferrule, or 2x (24... 14 AWG).

MPN