Siemens 3RV1011-0JA25 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1011-0JA25 SIRIUS Motor Protection CB, 1 A, CLASS

MPN3RV1011-0JA25

Siemens SIRIUS motor protection circuit breaker, 3RV1011-0JA25, 1 A continuous rated current, CLASS 10 trip class, 100 kA breaking capacity at 400 V, spring-loaded terminals, IP20 front protection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1011-0JA25 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker

Electrical

3RV1011-0JA25 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W

Protection & Tripping

3RV1011-0JA25 — Protection & Tripping
ParameterValue
Overload release setting range0.7 ... 1 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV1011-0JA25 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0

Connections

3RV1011-0JA25 — Connections
ParameterValue
Main-circuit terminal typespring-loaded terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.25 ... 1.5 mm²)
Conductor range, AWG (main contacts)2x (24 ... 14)

Mechanical

3RV1011-0JA25 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth81 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany

Environmental

3RV1011-0JA25 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m

Specifications

3RV1011-0JA25 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

The Siemens 3RV1011-0JA25 is a SIRIUS motor protection circuit breaker sized for a 0.25 kW motor at 400 V. It carries a 1 A continuous rated current and a CLASS 10 trip characteristic, meaning it clears overloads fast enough to protect standard induction motors during start-up without nuisance tripping. Phase failure detection is built in — critical for three-phase motor lines where a lost phase can cook the winding. Breaking capacity is 100 kA at 400 V AC, so this breaker can interrupt a bolted fault up to that level without upstream devices needing to clear it. That high SCCR simplifies panel coordination — no need for a larger upstream fuse just to protect this branch. Terminals are spring-loaded on both the main and auxiliary circuits, accepting 2x (0.25... 2.5 mm²) solid or 2x (24... 14) AWG stranded. Snap-on mounting onto 35 mm DIN rail per EN 50022, with 0 mm clearance needed at the sides or rear — zero-gap stacking on the rail. Mounting position is any. IP20 on the front face keeps fingers out.

Auxiliary Contact Ratings

The integrated auxiliary switch is rated 1 A at 24 V, 0.5 A at 230 V, and 0.15 A at 60 V. That covers PLC-level control signals and contactor coils in most panels. The transverse design means the contact block sits alongside the main body — no extra depth beyond the 81 mm listed.

Environmental & Compliance

Operating temperature range is -20 to +60 °C; storage and transport handle -50 to +80 °C. Shock rated at 25g / 11 ms. Surge voltage resistance is 6 kV. RoHS compliance date is 01.01.2013 — the part meets EU substance restrictions. Power loss in hot operating state is 5.5 W.

Frequently asked questions

What is 3RV1011-0JA25 used for?

It is a motor protection circuit breaker for a 0.25 kW motor at 400 V, with 1 A continuous rating and CLASS 10 trip. Use it to protect three-phase induction motors against overload and phase failure.

What is the breaking capacity of 3RV1011-0JA25?

100 kA at 240 V, 400 V, 500 V, and 690 V AC. That is a high short-circuit current rating for a 1 A breaker — it can clear a bolted fault without upstream coordination.

Will 3RV1011-0JA25 drop into a panel specified around 3RV1011-0HA10?

Both share the same 45 mm width, 90 mm height, and 35 mm DIN-rail mounting with zero side/back clearance. The terminal type and wire range are the same spring-loaded design. Mechanical fit is identical; verify the trip current rating matches your motor FLA.

Where can I buy 3RV1011-0JA25?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

MPN