Rated for 0.2 kW at 230 V and 1 hp at 460/480 V, it covers small motor loads common on pumps and conveyors. The interrupting rating hits 100 kA at 240 V, 400 V, and 500 V, dropping to 2 kA at 690 V. At 690 V the 2 kA rating still covers most industrial line-to-line faults. Depth is 75 mm, height 90 mm.
Clearance and backup fuse requirements
Clearance distances: 20 mm upwards and downwards, 9 mm at the side, 0 mm forwards and backwards. That zero forward clearance means it can sit flush against a panel door or gland plate without extra breathing space. Backup fuse depends on line voltage: none required at 240 V, gL/gG 20 A at 400 V, gL/gG 16 A at 500 V and 690 V. If the available fault current exceeds the breaker's 2 kA at 690 V, the 16 A gL/gG fuse upstream ensures coordinated interruption.
Termination and environmental limits
Main circuit terminals are M3 screw-type, accepting 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded wire. Maximum switching frequency 15 operations per hour in AC-3 and AC-3e duty. The voltage range is 20 to 690 V AC.