Skip to main content
Siemens 3RV1011-0KA15-ZI45 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1011-0KA15-ZI45 SIRIUS Motor Protection CB, CLASS

MPN3RV1011-0KA15-ZI45

Siemens SIRIUS 3RV1011-0KA15-ZI45 motor protection circuit breaker, size S00, CLASS 10, adjustable overload release 0.9…1.25 A, rated operating current 1.25 A, screw terminals, snap-on DIN rail mounting.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV1011-0KA15-ZI45 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV1011-0KA15-ZI45 — Electrical
ParameterValue
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W
3RV1011-0KA15-ZI45 — Protection & Tripping
ParameterValue
Trip classCLASS 10
3RV1011-0KA15-ZI45 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
3RV1011-0KA15-ZI45 — Mechanical
ParameterValue
Mounting positionany
3RV1011-0KA15-ZI45 — Specifications
ParameterValue
Design Of The ProductFor motor protection
3RV1011-0KA15-ZI45 — Other specifications
ParameterValue
Mountingscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
At 400 V rated value370 W
Operating current rated value1.25 A
Adjustable pick-up value current of the current-dependent overload release0.9 ... 1.25 A

Product details

The Siemens SIRIUS 3RV1011-0KA15-ZI45 is a motor protection circuit breaker in the S00 frame size, designed for screw and snap-on mounting onto 35 mm DIN rail per DIN EN 60715. Its CLASS 10 trip characteristic means it will disconnect within 10 seconds at 7.2× the set current — the standard for protecting standard induction motors during locked-rotor starts. The adjustable overload release spans 0.9 to 1.25 A, with a rated operating current of 1.25 A and a rated power of 370 W at 400 V.

Integration Notes

Power loss at rated current in hot operating state is 5.5 W total, 1.8 W per pole — factor that into enclosure thermal calculations when grouping multiple breakers. Screw-type terminals on top and bottom accept solid or stranded wire; torque to 0.8–1.2 N·m for main contacts.

Frequently asked questions

What is the trip class of 3RV1011-0KA15-ZI45?

CLASS 10 — it trips within 10 seconds at 7.2× the set overload current, matching the protection curve for standard squirrel-cage induction motors.

What is the adjustable current range on this breaker?

The current-dependent overload release adjusts from 0.9 to 1.25 A.

What mounting does 3RV1011-0KA15-ZI45 use?

Screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715. Mounting position is any.

Where can I buy 3RV1011-0KA15-ZI45?

Sourced and quoted to order against an RFQ through independent distribution channels; availability and current pricing confirmed at quote time.

MPN
3RV1011-0KA15-ZI45