Skip to main content
Siemens 3RV1011-1AA10-0FJ0-ZX95 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1011-1AA10-0FJ0-ZX95 SIRIUS Motor Circuit Breaker

MPN3RV1011-1AA10-0FJ0-ZX95

Siemens SIRIUS 3RV1011-1AA10-0FJ0-ZX95, motor-protective circuit breaker, 1.6 A rated continuous current, CLASS 10 trip class, 100 kA breaking capacity at 400 V AC, screw and snap-on DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV1011-1AA10-0FJ0-ZX95 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1011-1AA10-0FJ0-ZX95 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W
3RV1011-1AA10-0FJ0-ZX95 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)2 kA
Phase-failure detectionYes
Ground-fault detectionNo
3RV1011-1AA10-0FJ0-ZX95 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
3RV1011-1AA10-0FJ0-ZX95 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
3RV1011-1AA10-0FJ0-ZX95 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth81 mm
Mounting positionany
3RV1011-1AA10-0FJ0-ZX95 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
3RV1011-1AA10-0FJ0-ZX95 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

The Siemens 3RV1011-1AA10-0FJ0-ZX95 is a SIRIUS motor-protective circuit breaker designed to protect motor circuits against overload, short-circuit, and phase failure. It carries a rated continuous current of 1.6 A and a CLASS 10 trip class, meaning it will trip within 10 seconds at 7.2× the current setting — fast enough to protect a standard induction motor during a locked-rotor event. No ground-fault detection, so if that's required, you'll need a separate module or a different variant.

No clearance needed at the sides or rear. Mount in any orientation. Terminals accept solid or stranded copper: 2x (0.5–1.5 mm²) and 2x (0.75–2.5 mm²) per pole. AWG equivalents 2x (18–14) for the main contacts. Screw-type terminals — torque to the manufacturer's spec (not listed here).

Frequently asked questions

Where can I buy 3RV1011-1AA10-0FJ0-ZX95?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of this motor circuit breaker?

100 kA at 400 V AC. Also rated 100 kA at 240 V and 500 V, dropping to 2 kA at 690 V.

What motor power rating does this breaker support at 400 V?

0.55 kW at 400 V, which corresponds to a 1.6 A continuous setting.

MPN
3RV1011-1AA10-0FJ0-ZX95