Motor protection circuit breaker, 1.6 A, Class 10 — panel fit and ratings
The motor power rating is 0.55 kW at 400 V AC, sized for a small pump or conveyor motor. The 1.6 A continuous rating and Class 10 trip curve mean it will hold starting inrush for standard squirrel-cage motors without nuisance tripping, but will trip within 10 seconds at 7.2× rated current — per the Class 10 definition.
Termination and wiring — spring-loaded terminals, conductor range
Both the main current circuit and auxiliary/control circuit use spring-loaded terminals, accepting 2× (0.25 to 2.5 mm²) solid or 2× (24 to 14 AWG) stranded.
Environmental limits and surge withstand
Shock resistance is 25 g for 11 ms — suitable for machine-mounted panels near rotating equipment.