It combines short-circuit and overload protection in one device, with a Trip Class 10 thermal curve that matches standard induction motor starting profiles.
Mounting and fit
Clearance: 20 mm above and below, 9 mm to the side, zero forwards and backwards — tight panel packing is possible. Terminals are M3 screw-type for the main circuit, accepting 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded copper.
Protection and duty ratings
Ground fault detection is not included. Rated operational voltage covers 20 to 690 V. At 480 V the continuous current rating is 2 A; at 600 V also 2 A. Breaking capacity at 690 V drops to 2 kA. Maximum switching frequency in AC-3 (motor) duty is 15 operations per hour — fine for pump and fan cycling, not for high-speed jogging applications.