Skip to main content
Siemens 3RV1011-1CA20 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1011-1CA20 SIRIUS Motor Protection Breaker, 2.5 A

MPN3RV1011-1CA20

Siemens SIRIUS motor-protection circuit breaker, 3RV1011-1CA20, 2.5 A rated current, CLASS 10 trip class, 100 kA breaking capacity at 400 V AC, spring-loaded terminals, 45 mm width.

StockContact for availability
Lead timeCall for availability wk
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1011-1CA20 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker

Electrical

3RV1011-1CA20 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W

Protection & Tripping

3RV1011-1CA20 — Protection & Tripping
ParameterValue
Overload release setting range1.8 ... 2.5 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)10 kA
Breaking capacity at 690 V (AC)2 kA
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV1011-1CA20 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0

Connections

3RV1011-1CA20 — Connections
ParameterValue
Main-circuit terminal typespring-loaded terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.25 ... 1.5 mm²)
Conductor range, AWG (main contacts)2x (24 ... 14)

Mechanical

3RV1011-1CA20 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth81 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany

Environmental

3RV1011-1CA20 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m

Specifications

3RV1011-1CA20 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

SIRIUS 3RV1011-1CA20 — motor-protection breaker, 2.5 A, CLASS 10

The Siemens 3RV1011-1CA20 is a SIRIUS motor-protection circuit breaker rated for 2.5 A continuous current with a CLASS 10 trip characteristic, sized for a 0.75 kW motor at 400 V AC. It breaks up to 100 kA at 400 V AC, dropping to 10 kA at 500 V and 2 kA at 690 V — so it handles high-fault utility feeds downstream of a transformer but needs coordination check above 500 V. Phase-failure detection is built in; ground-fault detection is not. Spring-loaded terminals on both main and auxiliary circuits accept 2x (0.25 … 2.5 mm²) solid or 2x (0.25 … 1.5 mm²) finely stranded with ferrule — no screw torque to verify, just strip and push.

Panel fit and mounting

Snaps onto 35 mm DIN rail per EN 50022, 45 mm wide, 90 mm tall, 81 mm deep. Zero clearance needed at the back or sides — you can butt it against adjacent devices without derating the thermal capacity. Mounting position is any orientation. The IP20 front protection means it's safe for finger contact inside an enclosed panel but not for washdown or outdoor exposure.

Frequently asked questions

What is 3RV1011-1CA20's listed depth (81 mm) on this component line?

The depth is 81 mm, with zero clearance required at the back or sides — it can be mounted flush against adjacent devices on the DIN rail.

What is 3RV1011-1CA20's listed solid (2x (0.25 … 2.5 mm²)) on this component line?

The spring-loaded main terminals accept 2x (0.25 … 2.5 mm²) solid or 2x (0.25 … 1.5 mm²) finely stranded with ferrule. For AWG, that's 2x (24 … 14) for the main contacts.

Will 3RV1011-1CA20 drop into a panel that was specified around 3RV1011-1HA10 without rewiring?

Both share the same 45 mm width, DIN-rail mounting, and spring-loaded terminal family — so the physical footprint and wiring method are identical. The difference is in the trip curve and interrupting rating, not the panel cutout or terminal layout.

MPN
3RV1011-1CA20