Skip to main content
Siemens 3RV1011-1CA20-ZW97 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1011-1CA20-ZW97 SIRIUS Motor Protection Circuit B

MPN3RV1011-1CA20-ZW97

Siemens SIRIUS motor protection circuit breaker, 3RV1011-1CA20-ZW97, 2.5 A rated current, CLASS 10 trip class, 0.75 kW at 400 V, 100 kA breaking capacity at 400 V, spring-loaded terminals, 3-pole, IP20 front, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV1011-1CA20-ZW97 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1011-1CA20-ZW97 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W
3RV1011-1CA20-ZW97 — Protection & Tripping
ParameterValue
Overload release setting range1.8 ... 2.5 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)10 kA
Breaking capacity at 690 V (AC)2 kA
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV1011-1CA20-ZW97 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0
3RV1011-1CA20-ZW97 — Connections
ParameterValue
Main-circuit terminal typespring-loaded terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.25 ... 1.5 mm²)
Conductor range, AWG (main contacts)2x (24 ... 14)
3RV1011-1CA20-ZW97 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth81 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany
3RV1011-1CA20-ZW97 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m
3RV1011-1CA20-ZW97 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

The Siemens 3RV1011-1CA20-ZW97 is a SIRIUS motor protection circuit breaker rated for 2.5 A continuous current, with a CLASS 10 trip characteristic, sized for a 0.75 kW motor at 400 V three-phase. The IP20 front means it's finger-safe for panel builders working live.

Trip class and motor protection

It includes phase failure detection, so if you lose a phase on a lightly loaded motor, the breaker trips rather than letting the motor single-phase and burn. Rated operating frequency is 15 operations per hour maximum at AC-3 duty, which covers most conveyor and pump starts but not frequent jogging or reversing cycles.

Backwards clearance is 0 mm, so it can sit flush against the back panel. Spring-loaded terminals accept 2x (0.25 to 2.5 mm²) solid or 2x (0.25 to 1.5 mm²) finely stranded with ferrules. AWG equivalent is 2x (24 to 14). No screw torque to worry about — strip and push.

Shock rated at 25g for 11 ms.

Frequently asked questions

Where can I buy 3RV1011-1CA20-ZW97 and get a price?

It is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the trip class and what does it mean?

CLASS 10 means the breaker trips within 10 seconds at 7.2× the current setting, matching standard DOL motor starts.

What is the breaking capacity at 400 V?

100 kA at 400 V AC, which is high enough for most industrial panels without needing upstream current-limiting fuses.

Does it include phase failure protection?

Yes, phase failure detection is built in — it will trip if a phase is lost on a lightly loaded motor.

What wire sizes does the spring terminal accept?

Solid: 2x (0.25 to 2.5 mm²); finely stranded with ferrule: 2x (0.25 to 1.5 mm²); AWG: 2x (24 to 14).

MPN
3RV1011-1CA20-ZW97