Skip to main content
Siemens 3RV1011-1DA10-0FJ0-ZX95 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1011-1DA10-0FJ0-ZX95 SIRIUS Motor Protection Circ

MPN3RV1011-1DA10-0FJ0-ZX95

Siemens SIRIUS motor protection circuit breaker, 3RV1011-1DA10-0FJ0-ZX95, 3.2 A continuous current, CLASS 10 trip class, 100 kA breaking capacity at 400 V AC, phase failure detection, screw-type terminals, DIN rail snap-on mounting.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1011-1DA10-0FJ0-ZX95 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker

Electrical

3RV1011-1DA10-0FJ0-ZX95 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W

Protection & Tripping

3RV1011-1DA10-0FJ0-ZX95 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)3 kA
Breaking capacity at 690 V (AC)2 kA
Phase-failure detectionYes
Ground-fault detectionNo

Endurance & Switching

3RV1011-1DA10-0FJ0-ZX95 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h

Connections

3RV1011-1DA10-0FJ0-ZX95 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)

Mechanical

3RV1011-1DA10-0FJ0-ZX95 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth81 mm
Mounting positionany

Environmental

3RV1011-1DA10-0FJ0-ZX95 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C

Specifications

3RV1011-1DA10-0FJ0-ZX95 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

The Siemens SIRIUS 3RV1011-1DA10-0FJ0-ZX95 is a motor protection circuit breaker rated for 3.2 A continuous current with a CLASS 10 trip characteristic, meaning it disconnects within 10 seconds at 7.2× rated current — fast enough to protect standard induction motors during stall or overload without nuisance tripping on normal startup inrush. Phase failure detection is built in, so on a three-phase motor losing one leg, the breaker trips before single-phasing damages the winding. No ground-fault detection on this variant. Breaking capacity runs 100 kA at 240 V and 400 V AC, then drops to 3 kA at 500 V and 2 kA at 690 V AC — the 100 kA figure handles high-fault utility feeds; the lower 690 V rating still clears faults on 690 V industrial networks.

Mounts via screw or snap-on onto 35 mm DIN rail per EN 50022. Dimensions are 45 mm wide, 90 mm tall, 81 mm deep — fits a standard 45 mm modular slot, leaving room for adjacent breakers or contactors in a motor starter lineup. Screw-type terminals on the main circuit accept 2x (0.5…1.5 mm²) solid or stranded, or 2x (0.75…2.5 mm²) — common panel wire sizes. The auxiliary switch option is present on this unit (: Yes). Rated for any mounting position, operating ambient -20 to +60 °C, storage/transport -50 to +80 °C. Shock rated 25g / 11 ms. IP20 on the front — protected against finger contact, not washdown.

Power dissipation at AC in hot operating state is 7.25 W total, 2.4 W per pole — factor that into enclosure thermal calculations if grouping multiple breakers in a sealed panel.

Frequently asked questions

Where can I buy 3RV1011-1DA10-0FJ0-ZX95 and get a price?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the listed depth of 3RV1011-1DA10-0FJ0-ZX95?

81 mm depth, with a width of 45 mm and height of 90 mm — fits a standard 45 mm DIN-rail slot.

Does 3RV1011-1DA10-0FJ0-ZX95 include phase failure protection?

Yes, phase failure detection is built in — it trips on loss of one phase to prevent single-phasing damage on three-phase motors.

What compliance documentation is available for this part?

The part carries Siemens SIRIUS documentation including RoHS and REACH compliance declarations, and is designed to meet IEC/EN 60947 standards for motor protection circuit breakers. Specific certificates (UL, CSA) should be confirmed at quote time.

MPN
3RV1011-1DA10-0FJ0-ZX95