Motor protection breaker, S00 frame, CLASS 10
The adjustable overload release covers 2.2 to 3.2 A, set via a dial on the front; the fixed magnetic short-circuit release trips at 42 A, clearing faults up to 100 kA at 400 V AC.
Mounts in any position on 35 mm DIN rail — the S00 footprint is 45 mm wide, 75 mm deep (excluding terminals), with 20 mm clearance above and below for wire bending. Screw terminals accept 2×(0.75 to 2.5 mm²) solid or stranded, or 2×4 mm². Torque to 0.8–1.2 N·m.