Motor-protection circuit breaker, 3.2 A, Class 10 — SIRIUS
Breaking capacity reaches 100 kA at 240 V and 400 V AC, dropping to 3 kA at 500 V and 2 kA at 690 V — the high 100 kA figure at 400 V means it can be used on high-fault-capacity industrial networks without requiring an upstream current-limiting fuse for most installations.
RoHS substance prohibition date is 01/01/2013.
Auxiliary switch and wiring
The auxiliary switch is transverse design and the product extension for an auxiliary switch is available. Main and control circuit terminals are screw-type, accepting solid and stranded conductors: 2x (0.5...1.5 mm²) and 2x (0.75...2.5 mm²). Auxiliary contact ratings: 1 A at 24 V, 0.5 A at 230 V, 0.15 A at 60 V — these are the switching capacities for the signal circuit, not the main motor current.