Motor protection circuit breaker, 3.2 A, CLASS 10 — panel integration note
It snaps onto a 35 mm DIN rail per DIN EN 50022 and accepts spring-loaded terminals for the main circuit — solid or stranded 0.25 to 2.5 mm² (2x).
Breaking capacity and fault handling
Rated breaking capacity hits 100 kA at 240 V and 400 V AC, dropping to 3 kA at 500 V and 2 kA at 690 V. No ground fault detection on this variant.
Electrical endurance and switching frequency
The main contacts are rated for 100,000 typical electrical operations under AC load. Maximum switching frequency in AC-3 duty is 15 operations per hour — enough for a conveyor start/stop cycle but not for a rapid-reversing application.
Mounting position is any orientation — no derating needed for horizontal or vertical panel placement. Shock resistance is 25g for 11 ms, which covers most industrial vibration environments.