The adjustable overload release is set for 2.8...4 A, and the magnetic short-circuit release trips at 52 A. At 400 V AC-3 duty it switches 4 A, corresponding to a 1.5 kW motor — that's the rating that decides the motor size it protects, not the raw thermal current.
Clearance: 20 mm above and below, 9 mm at the sides, zero forward or backward — so it sits flush against the backpanel. IP20 finger-safe front per IEC 60529, meaning the busbars are protected from accidental contact in an open panel.
RoHS compliant per the substance prohibition date of 01.01.2013. The front face is finger-safe to IP20 per IEC 60529.