Screw-type terminals on the main circuit accept 2×(0.5…1.5 mm²) solid or stranded, or 2×(0.75…2.5 mm²). Clearance requirements: 20 mm upwards and downwards, 9 mm at the sides, zero forwards and backwards — so it can be packed tightly in a multi-row enclosure.
Rated operational voltage covers 20…690 V. At 230 V it handles 0.33 hp; at 200/208 V, 0.8 hp; at 220/230 V, 0.75 hp. Maximum switching rate in AC-3 duty is 15 operations per hour. For backup fuse coordination: at 400 V use gL/gG 40 A; at 500 V and 690 V use gL/gG 35 A. At 240 V no backup fuse is required.