Skip to main content
Siemens 3RV1011-1EA10-ZW97 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1011-1EA10-ZW97 SIRIUS Motor Protection Circuit B

MPN3RV1011-1EA10-ZW97
Active

Siemens SIRIUS 3RV1011-1EA10-ZW97 motor protection circuit breaker, Class 10, 100 kA breaking capacity at 400 V, 45 mm wide, screw terminals.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1011-1EA10-ZW97 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00

Electrical

3RV1011-1EA10-ZW97 — Electrical
ParameterValue
Rated operational current (Ie)4 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W

Protection & Tripping

3RV1011-1EA10-ZW97 — Protection & Tripping
ParameterValue
Overload release setting range2.8 ... 4 A
Instantaneous short-circuit trip current52 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)3 kA
Breaking capacity at 690 V (AC)2 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V2 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV1011-1EA10-ZW97 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0

Connections

3RV1011-1EA10-ZW97 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)

Mechanical

3RV1011-1EA10-ZW97 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth75 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany

Environmental

3RV1011-1EA10-ZW97 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m

Specifications

3RV1011-1EA10-ZW97 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

What it is and where it fits

The Siemens 3RV1011-1EA10-ZW97 is a SIRIUS motor protection circuit breaker designed for motor protection duty. It snaps onto a 35 mm DIN rail per DIN EN 60715, so it integrates into any standard control panel enclosure. At 45 mm wide, 90 mm tall, and 75 mm deep, it leaves room for adjacent contactors and overloads in a motor starter lineup.

Key ratings and what they mean for your motor circuit

Trip Class 10 means this breaker clears a stalled-rotor condition within 10 seconds at 7.2× rated current — the standard for standard-duty induction motors driving pumps, fans, and conveyors. The 100 kA breaking capacity at both 240 V and 400 V gives you full selectivity with upstream fuses or a main breaker; you won't cascade a fault to the bus. Phase failure detection is built in, so a lost phase on the line side trips the breaker before single-phasing cooks the motor winding. Rated operational voltage spans 20 to 690 V, covering most low-voltage motor circuits. The screw-type terminals accept 2×(0.5 to 1.5 mm²) or 2×(0.75 to 2.5 mm²) solid or stranded — standard panel wire sizes, no special ferrules needed. Mounting position is any, which helps when the panel layout forces a sideways or inverted fit.

Frequently asked questions

Will 3RV1011-1EA10-ZW97 drop into a panel specified around 3RV1011-1HA10 without rewiring?

Both share the same SIRIUS 3RV10 family footprint — 45 mm wide, same DIN-rail mounting, same screw-terminal pattern. The -ZW97 is a special version; the base mechanical fit is identical, so no panel rework or rewiring is needed for the swap.

MPN
3RV1011-1EA10-ZW97