Skip to main content
Siemens 3RV1011-1EA20 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1011-1EA20 SIRIUS Motor Protection Circuit Breake

MPN3RV1011-1EA20

Siemens SIRIUS motor protection circuit breaker, 3RV1011-1EA20, 4 A rated continuous current, CLASS 10 trip class, 100 kA breaking capacity at 400 V AC, spring-loaded terminals, 45 x 90 x 81 mm.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1011-1EA20 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker

Electrical

3RV1011-1EA20 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W

Protection & Tripping

3RV1011-1EA20 — Protection & Tripping
ParameterValue
Overload release setting range2.8 ... 4 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)3 kA
Breaking capacity at 690 V (AC)2 kA
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV1011-1EA20 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0

Connections

3RV1011-1EA20 — Connections
ParameterValue
Main-circuit terminal typespring-loaded terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.25 ... 1.5 mm²)
Conductor range, AWG (main contacts)2x (24 ... 14)

Mechanical

3RV1011-1EA20 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth81 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany

Environmental

3RV1011-1EA20 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m

Specifications

3RV1011-1EA20 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

Motor protection circuit breaker, 4 A, Class 10

The Siemens SIRIUS 3RV1011-1EA20 is a motor protection circuit breaker rated for a continuous current of 4 A with a CLASS 10 trip characteristic, meaning it will trip within 10 seconds at 7.2× rated current — fast enough to protect standard induction motors during a stall or locked-rotor condition without nuisance tripping on normal starting inrush. Breaking capacity reaches 100 kA at both 240 V and 400 V AC, dropping to 3 kA at 500 V and 2 kA at 690 V — so on a 400 V line this breaker handles fault currents large enough to sit downstream of most distribution transformers without needing a current-limiting upstream device. Phase failure detection is built in, which prevents single-phasing damage on a three-phase motor load — common in older plants where a blown fuse on one phase might otherwise go unnoticed until the motor burns.

Mounting and integration

Snap-on mounting onto 35 mm DIN rail per EN 50022, or screw-fix to a backplate — zero clearance needed at the sides or rear (0 mm backwards, 0 mm at the side), so it packs tight in a panel without derating for air circulation. Dimensions are 45 mm wide, 90 mm tall, 81 mm deep — fits a standard 45 mm module slot on the rail. Spring-loaded terminals on both main and auxiliary circuits accept 2x (0.25... 2.5 mm²) solid or 2x (0.25... 1.5 mm²) finely stranded with ferrule. IP20 finger-safe protection on the front face; suitable for enclosed panel use where operators might reach in during maintenance.

Lifecycle and compliance

RoHS compliance date marked as 01.01.2013 — the part meets the EU RoHS directive effective from that date. Surge voltage resistance rated at 6 000 V, which covers the impulse withstand for industrial control panels per IEC 60947.

Frequently asked questions

Where can I buy 3RV1011-1EA20 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution channels. Submit a request for quote; availability and current pricing are confirmed at quote time.

Will 3RV1011-1EA20 drop into a panel specified around 3RV1011-1HA10 without rewiring?

Both are 45 mm wide SIRIUS breakers with the same DIN-rail footprint and spring-loaded terminal layout, so physical fit and wiring should be identical. The difference is the current rating and trip setting — verify your load current against the 4 A rating of this unit before swapping.

What compliance documentation does this brand provide for 3RV1011-1EA20?

The part carries a RoHS compliance date of 01.01.2013, indicating it meets the EU RoHS directive. Surge voltage resistance is rated at 6 000 V, consistent with IEC 60947-1 impulse withstand requirements for industrial control gear.

MPN
3RV1011-1EA20