Motor protection circuit breaker — SIRIUS 3RV1011-1FA10-ZW98
The phase failure detection is a hard requirement for three-phase motor circuits: if one phase drops, the breaker trips, preventing single-phasing damage. The 100 kA SCCR at 400 V and 240 V is the interrupting rating; at 690 V it drops to 2 kA, so verify your fault-current study at the service voltage.
Screw-type terminals for the main circuit accept 2×(0.5–1.5 mm²) or 2×(0.75–2.5 mm²) solid or stranded. Clearance: 20 mm above and below, 9 mm to the side.