Skip to main content
Siemens 3RV1011-1FA20-ZW98 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1011-1FA20-ZW98 SIRIUS Motor Protection Circuit B

MPN3RV1011-1FA20-ZW98

Siemens SIRIUS motor protection circuit breaker, 3RV1011-1FA20-ZW98, 5 A continuous, CLASS 10, 100 kA breaking at 400 V, 3-pole, spring-loaded terminals, screw and snap-on DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1011-1FA20-ZW98 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker

Electrical

3RV1011-1FA20-ZW98 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W

Protection & Tripping

3RV1011-1FA20-ZW98 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)3 kA
Breaking capacity at 690 V (AC)2 kA
Phase-failure detectionYes
Ground-fault detectionNo

Endurance & Switching

3RV1011-1FA20-ZW98 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h

Connections

3RV1011-1FA20-ZW98 — Connections
ParameterValue
Main-circuit terminal typespring-loaded terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.25 ... 1.5 mm²)

Mechanical

3RV1011-1FA20-ZW98 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth81 mm
Mounting positionany

Environmental

3RV1011-1FA20-ZW98 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C

Specifications

3RV1011-1FA20-ZW98 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

What this breaker does in the panel

The Siemens 3RV1011-1FA20-ZW98 is a 3-pole SIRIUS motor protection circuit breaker rated for 5 A continuous current with CLASS 10 trip characteristic — meaning it protects motor circuits against overload and short-circuit, tripping fast enough for standard induction motors up to 1.5 kW at 400 V. It breaks up to 100 kA at 400 V, so it handles high-fault-current panels without needing an upstream fuse for SCCR compliance. Phase failure detection is built in; ground fault detection is not. The main circuit uses spring-loaded terminals accepting 2x (0.25... 2.5 mm²) solid or 2x (0.25... 1.5 mm²) fine-stranded with ferrule, AWG 24–14. No auxiliary contacts are fitted on this variant.

Mounting and integration

Mounts via screw or snap-on onto 35 mm DIN rail per EN 50022; any mounting position works. The 45 mm width and 90 mm height fit a standard 4-module slot; depth is 81 mm. Zero clearance needed at the sides or rear — 0 mm backwards and 0 mm at the side — so you can pack breakers tight in a row. Front face is IP20.

Frequently asked questions

Where can I buy 3RV1011-1FA20-ZW98 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing.

Will 3RV1011-1FA20-ZW98 drop into a panel specified around 3RV1011-1HA10 without rewiring?

Both are 3-pole SIRIUS motor protection breakers with the same 45 mm width, 90 mm height, 81 mm depth, and DIN rail mount. The 1FA20 carries a 5 A continuous rating and CLASS 10 trip; the 1HA10 is a different rating. If the load current matches, the mechanical fit is identical — no rewiring for the footprint.

What is the depth of 3RV1011-1FA20-ZW98?

The depth is 81 mm.

What conductor sizes does the main circuit accept?

Solid: 2x (0.25... 2.5 mm²); fine-stranded with ferrule: 2x (0.25... 1.5 mm²); AWG: 2x (24... 14).

MPN
3RV1011-1FA20-ZW98