Skip to main content
Siemens 3RV1011-1GA10-0FJ0-ZX95 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1011-1GA10-0FJ0-ZX95 SIRIUS Motor Protection Circ

MPN3RV1011-1GA10-0FJ0-ZX95

Siemens SIRIUS motor protection circuit breaker, 3RV1011-1GA10-0FJ0-ZX95, 6.3 A continuous current, CLASS 10 trip, 100 kA breaking capacity at 400 V AC, screw-type terminals, screw and snap-on mounting on 35 mm DIN rail.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1011-1GA10-0FJ0-ZX95 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker

Electrical

3RV1011-1GA10-0FJ0-ZX95 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W

Protection & Tripping

3RV1011-1GA10-0FJ0-ZX95 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)3 kA
Breaking capacity at 690 V (AC)2 kA
Phase-failure detectionYes
Ground-fault detectionNo

Endurance & Switching

3RV1011-1GA10-0FJ0-ZX95 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h

Connections

3RV1011-1GA10-0FJ0-ZX95 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)

Mechanical

3RV1011-1GA10-0FJ0-ZX95 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth81 mm
Mounting positionany

Environmental

3RV1011-1GA10-0FJ0-ZX95 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C

Specifications

3RV1011-1GA10-0FJ0-ZX95 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

Motor Protection Circuit Breaker for the Panel Builder

The Siemens SIRIUS 3RV1011-1GA10-0FJ0-ZX95 is a motor protection circuit breaker designed for the 6.3 A continuous current range, sized for a 2.2 kW motor at 400 V. It carries a CLASS 10 trip characteristic, meaning it will trip within 10 seconds at 7.2× rated current — fast enough to protect standard induction motors on a conveyor or pump start without nuisance tripping on the inrush. The 100 kA breaking capacity at 400 V AC gives it the interrupting capability to handle high-fault-current panels, so it can be used as a branch-circuit protective device without needing an upstream current-limiting fuse in many installations. Phase failure detection is built in, so if one leg drops out on a three-phase motor, the breaker opens before single-phasing cooks the winding. Mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 50022, and the IP20 finger-safe front cover keeps live terminals out of reach in an open panel.

Breaking Capacity and Coordination

The 100 kA breaking capacity at 400 V AC is the headline number, but note the derating at higher voltages: 3 kA at 500 V and 2 kA at 690 V. That means if your panel feeds a 690 V motor, this breaker still interrupts faults, but you need to verify the available fault current at that voltage doesn't exceed 2 kA. The 6 kV rated surge voltage resistance confirms it handles switching transients on a 400 V system without flashover.

Integration and Wiring

Screw-type terminals accept 2x (0.5...1.5 mm²) solid or 2x (0.75...2.5 mm²) stranded conductors, AWG 2x (18...14). 45 mm width, 90 mm height. Any mounting position; -20 to +60 °C operating range.

MPN
3RV1011-1GA10-0FJ0-ZX95