Skip to main content
Siemens 3RV1011-1GA10-ZI45 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1011-1GA10-ZI45 SIRIUS Motor Protection Circuit B

MPN3RV1011-1GA10-ZI45

Siemens SIRIUS, motor protection circuit breaker, size S00, CLASS 10, adjustable overload release 4.5–6.3 A, screw terminals, standard switching capacity, order code 3RV1011-1GA10-ZI45.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1011-1GA10-ZI45 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00

Electrical

3RV1011-1GA10-ZI45 — Electrical
ParameterValue
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W

Protection & Tripping

3RV1011-1GA10-ZI45 — Protection & Tripping
ParameterValue
Trip classCLASS 10

Connections

3RV1011-1GA10-ZI45 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom

Mechanical

3RV1011-1GA10-ZI45 — Mechanical
ParameterValue
Mounting positionany

Specifications

3RV1011-1GA10-ZI45 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Other specifications

3RV1011-1GA10-ZI45 — Other specifications
ParameterValue
Mountingscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
At 400 V rated value2 200 W
Operating current rated value6.3 A
Adjustable pick-up value current of the current-dependent overload release4.5 ... 6.3 A

Product details

What this part is and where it fits

The Siemens SIRIUS 3RV1011-1GA10-ZI45 is a motor protection circuit breaker in size S00, designed to protect three-phase motor circuits against overload and short-circuit faults. It carries a CLASS 10 trip class, meaning it will trip within 10 seconds under a locked-rotor condition — fast enough to protect standard induction motors during start-up without nuisance tripping. The overload release is adjustable from 4.5 A to 6.3 A, and the rated operating current is 6.3 A, so it fits motors in that full-load current band. Mounting is via screw and snap-on onto 35 mm DIN rail per DIN EN 60715, and the mounting position is any — no derating needed for horizontal or vertical orientation in the panel.

Integration notes

Screw-type terminals on the main current circuit accept solid or stranded copper; the S00 frame keeps the width to 45 mm, so it fits a standard DIN-rail footprint alongside contactors and auxiliary blocks. Power loss at rated current in hot operating state is 7.25 W total (2.4 W per pole), which is low enough that no special ventilation is needed in a typical IP20 enclosure.

Frequently asked questions

What is the trip class of 3RV1011-1GA10-ZI45?

CLASS 10 — it trips within 10 seconds under locked-rotor conditions, matching standard motor protection requirements.

What is the adjustable overload range on this breaker?

The current-dependent overload release is adjustable from 4.5 A to 6.3 A.

MPN
3RV1011-1GA10-ZI45