Skip to main content
Siemens 3RV1011-1GA15-0BA0 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1011-1GA15-0BA0 SIRIUS Motor Protection Circuit B

MPN3RV1011-1GA15-0BA0
Active

Siemens SIRIUS motor protection circuit breaker, 3RV1011-1GA15-0BA0, 6.3 A rated continuous current, Class 10 thermal overload, magnetic short-circuit trip, 100 kA breaking capacity at 400 V AC, screw terminals, snap-on 35 mm DIN rail.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1011-1GA15-0BA0 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker

Electrical

3RV1011-1GA15-0BA0 — Electrical
ParameterValue
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W

Protection & Tripping

3RV1011-1GA15-0BA0 — Protection & Tripping
ParameterValue
Overload release setting range4.5 ... 6.3 A
Instantaneous short-circuit trip current82 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)3 kA
Breaking capacity at 690 V (AC)2 kA
Short-circuit trip typemagnetic
Overload release typethermal
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV1011-1GA15-0BA0 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0

Connections

3RV1011-1GA15-0BA0 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (18 ... 14)

Mechanical

3RV1011-1GA15-0BA0 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth81 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany

Environmental

3RV1011-1GA15-0BA0 — Environmental
ParameterValue
Operating temperature-50 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m

Specifications

3RV1011-1GA15-0BA0 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

The Siemens SIRIUS 3RV1011-1GA15-0BA0 is a motor protection circuit breaker designed for thermal-magnetic overload and short-circuit protection of motors up to 2.2 kW at 400 V. Rated continuous current is 6.3 A, with a Trip Class 10 thermal release — meaning it trips within 10 seconds at 7.2× the set current, standard for protecting standard induction motors during start-up. The magnetic short-circuit trip (fixed) handles fault currents up to 100 kA at 400 V AC, so it can be used on high-fault-capacity mains without an upstream current-limiting fuse in many cases. Mounting is screw and snap-on onto 35 mm standard mounting rail per DIN EN 50022. The 45 mm width fits a standard 45 mm modular device slot. Front IP20 protection means it's safe for finger contact inside a closed panel but not for washdown environments. Operating temperature range is -50 to +60 °C, storage -50 to +80 °C.

Screw terminals accept solid conductors 2x (0.5...1.5 mm²) and 2x (0.75...2.5 mm²), or stranded equivalents. AWG for main contacts is 2x (18...14). No ground-fault detection; phase-failure detection is built in. The auxiliary switch is transverse — verify orientation when ordering separate aux blocks. Mounting position is any; shock resistance 25g / 11 ms. Power dissipation at rated current in hot operating state is 7.25 W — account for that heat in a densely packed enclosure.

MPN
3RV1011-1GA15-0BA0