Ratings that matter for fit
The 45 mm width keeps it compact in a multi-breaker lineup. Wire range accepts 2×(0.5…1.5 mm²) solid or 2×(0.75…2.5 mm²) stranded — covers most motor feeder sizes up to the breaker's rating. Short-circuit breaking capacity varies with line voltage: 100 kA at 240 V, 13 kA at 400 V, 3 kA at 500 V, and 2 kA at 690 V.
Panel integration
Clearance: 20 mm above and below, 9 mm to the side, zero forward clearance needed.