Siemens SIRIUS 3RV1011-1HA15-0BA0, motor-protective circuit breaker, 8 A continuous, 3 kW at 400 V, CLASS 10 trip, screw terminals, IP20 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1011-1HA15-0BA0 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker

Electrical

3RV1011-1HA15-0BA0 — Electrical
ParameterValue
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)9.25 W
Power loss, per pole (AC, hot)3.1 W

Protection & Tripping

3RV1011-1HA15-0BA0 — Protection & Tripping
ParameterValue
Overload release setting range5.5 ... 8 A
Instantaneous short-circuit trip current104 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)50 kA
Breaking capacity at 500 V (AC)3 kA
Breaking capacity at 690 V (AC)2 kA
Short-circuit trip typemagnetic
Overload release typethermal
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV1011-1HA15-0BA0 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0

Connections

3RV1011-1HA15-0BA0 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (18 ... 14)

Mechanical

3RV1011-1HA15-0BA0 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth81 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany

Environmental

3RV1011-1HA15-0BA0 — Environmental
ParameterValue
Operating temperature-50 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m

Specifications

3RV1011-1HA15-0BA0 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

The Siemens SIRIUS 3RV1011-1HA15-0BA0 is a motor-protective circuit breaker rated for 8 A continuous current and 3 kW at 400 V. Its CLASS 10 trip characteristic means it clears a stalled-rotor overload fast enough to protect standard squirrel-cage induction motors without nuisance tripping on normal starting inrush. Short-circuit breaking capacity runs 100 kA at 240 V, 50 kA at 400 V, 3 kA at 500 V, and 2 kA at 690 V — enough headroom for most panel feeds downstream of a transformer or distribution board. Built-in phase-failure detection catches a lost leg before the motor single-phases to a smoking stop. That alone saves a bearing replacement route call.

Mounting and Terminals

Snaps onto 35 mm DIN rail per EN 50022. Screw-type terminals on both main and auxiliary circuits. Solid wire accepted: 2x (0.5 to 1.5 mm²) and 2x (0.75 to 2.5 mm²); stranded same. AWG equivalents for main contacts: 2x (18 to 14). IP20 on the front face — fine inside a closed panel, but keep it out of washdown zones. Mounting position is any orientation.

Frequently asked questions

What is the breaking capacity of 3RV1011-1HA15-0BA0 at 400 V?

50 kA at 400 V AC. That's the short-circuit current it can safely interrupt at that voltage level.

What wire sizes does the 3RV1011-1HA15-0BA0 accept?

Solid and stranded: 2x (0.5 to 1.5 mm²) and 2x (0.75 to 2.5 mm²). For AWG on main contacts: 2x (18 to 14).

Where can I buy 3RV1011-1HA15-0BA0 and get a price?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
3RV1011-1HA15-0BA0