Skip to main content
Siemens 3RV1011-1HA15-ZI45 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1011-1HA15-ZI45 SIRIUS Motor Protection CB, CLASS

MPN3RV1011-1HA15-ZI45

Siemens SIRIUS, motor protection circuit breaker, size S00, CLASS 10, adjustable overload release 5.5...8 A, magnetic short-circuit trip 104 A, screw terminals, standard switching capacity, 3RV1011-1HA15-ZI45.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV1011-1HA15-ZI45 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV1011-1HA15-ZI45 — Electrical
ParameterValue
Power loss (AC, hot)9.25 W
Power loss, per pole (AC, hot)3.1 W
3RV1011-1HA15-ZI45 — Protection & Tripping
ParameterValue
Trip classCLASS 10
3RV1011-1HA15-ZI45 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
3RV1011-1HA15-ZI45 — Mechanical
ParameterValue
Mounting positionany
3RV1011-1HA15-ZI45 — Specifications
ParameterValue
Design Of The ProductFor motor protection
3RV1011-1HA15-ZI45 — Other specifications
ParameterValue
Mountingscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
At 400 V rated value3 000 W
Operating current rated value8 A
Adjustable pick-up value current of the current-dependent overload release5.5 ... 8 A

Product details

The adjustable overload release is set via a dial from 5.5 A to 8 A, letting you match the breaker to the motor nameplate FLA without swapping hardware. The S00 footprint (45 mm wide) fits standard panel layouts and leaves room for adjacent contactors in a motor starter stack.

This breaker combines a thermal bimetal overload release (CLASS 10) with a magnetic instantaneous short-circuit trip set at 104 A. The thermal element protects against sustained overloads and phase-loss conditions; the magnetic element clears a bolted fault at 104 A without waiting for the thermal curve. At 400 V AC the unit is rated for 3,000 W motor output, and the switching capacity at 400 V is 50 kA (per the SIRIUS family rating for this size). Power dissipation is 9.25 W total in hot operating state, 3.1 W per pole — relevant for enclosure thermal calculations when grouping multiple breakers in a panel.

Frequently asked questions

What is the trip class of 3RV1011-1HA15-ZI45?

CLASS 10, meaning it trips within 10 seconds at 7.2× the current setting — suitable for standard induction motor starting profiles.

What is the adjustable overload range on this breaker?

The current-dependent overload release is adjustable from 5.5 A to 8 A via a front dial.

Where can I buy 3RV1011-1HA15-ZI45 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing.

Will 3RV1011-1HA15-ZI45 drop into a panel specified around 3RV1011-1HA10?

Both are size S00, same DIN rail mounting, same screw terminal arrangement, and same 45 mm width. The main difference is the overload range: 5.5...8 A on this unit versus a different range on the 1HA10. If the motor FLA falls within 5.5...8 A, it is a direct mechanical and electrical swap without rewiring.

MPN
3RV1011-1HA15-ZI45