Siemens 3RV1011-1KA10-ZW95 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1011-1KA10-ZW95 SIRIUS Motor Protection Circuit B

MPN3RV1011-1KA10-ZW95

Siemens SIRIUS motor protection circuit breaker, 3RV1011-1KA10-ZW95, Class 10 trip, 45 mm wide, screw and snap-on 35 mm DIN rail mount, current lifecycle.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1011-1KA10-ZW95 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00

Electrical

3RV1011-1KA10-ZW95 — Electrical
ParameterValue
Rated operational current (Ie)12.5 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)9.25 W
Power loss, per pole (AC, hot)3.1 W

Protection & Tripping

3RV1011-1KA10-ZW95 — Protection & Tripping
ParameterValue
Overload release setting range9 ... 12.5 A
Instantaneous short-circuit trip current156 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)50 kA
Breaking capacity at 500 V (AC)3 kA
Breaking capacity at 690 V (AC)2 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V2 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV1011-1KA10-ZW95 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0

Connections

3RV1011-1KA10-ZW95 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)

Mechanical

3RV1011-1KA10-ZW95 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth75 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany

Environmental

3RV1011-1KA10-ZW95 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m

Specifications

3RV1011-1KA10-ZW95 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

The Siemens SIRIUS 3RV1011-1KA10-ZW95 is a motor protection circuit breaker designed for Class 10 trip characteristics. It mounts via screw and snap-on onto 35 mm DIN rail per DIN EN 60715, fitting standard panel layouts without extra hardware. Rated for breaking capacities of 100 kA at 240 V, 13 kA at 400 V, 3 kA at 500 V, and 2 kA at 690 V, this breaker handles fault currents typical in industrial motor circuits. The Class 10 trip curve means it disconnects within 10 seconds at 600% of the thermal setting, protecting standard induction motors from overload without nuisance tripping on startup inrush. Phase failure detection is built in, so the breaker trips if one phase drops out — preventing single-phasing damage on a three-phase motor. Screw-type terminals accept 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded copper, which covers most motor branch-circuit wiring sizes.

Mounting and Fit

At 45 mm wide and 90 mm tall, this breaker occupies a single modular space on the DIN rail. The 75 mm depth leaves clearance for wiring behind the panel door. Mounting position is any orientation; the specified clearances are 20 mm upward and downward, 9 mm to the side, and 0 mm forward or backward — meaning it can sit tight against the backplane.

Frequently asked questions

Where can I buy 3RV1011-1KA10-ZW95?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quoting.

What is the breaking capacity of 3RV1011-1KA10-ZW95 at 400 V?

The breaking capacity at 400 V is 13 kA. At 240 V it is 100 kA, at 500 V it is 3 kA, and at 690 V it is 2 kA.

Does 3RV1011-1KA10-ZW95 include phase failure detection?

Yes, phase failure detection is built in. The breaker will trip if one phase is lost, protecting the motor from single-phasing damage.

MPN