Siemens 3RV1011-1KA15 — Motor Protection Circuit Breakers (MPCB)

Siemens SIRIUS 3RV1011-1KA15 Circuit Breaker, CLASS 10, 100

MPN3RV1011-1KA15
Active

Siemens SIRIUS 3RV1011-1KA15 circuit breaker, CLASS 10 trip class, 100 kA breaking capacity at 240 V, 2 hp motor rating at 230 V, screw and snap-on mounting on 35 mm DIN rail.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1011-1KA15 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00

Electrical

3RV1011-1KA15 — Electrical
ParameterValue
Rated operational current (Ie)12 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)9.25 W
Power loss, per pole (AC, hot)3.1 W

Protection & Tripping

3RV1011-1KA15 — Protection & Tripping
ParameterValue
Overload release setting range9 ... 12.5 A
Instantaneous short-circuit trip current156 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)50 kA
Breaking capacity at 500 V (AC)3 kA
Breaking capacity at 690 V (AC)2 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V2 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV1011-1KA15 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0

Connections

3RV1011-1KA15 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)

Mechanical

3RV1011-1KA15 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth75 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany

Environmental

3RV1011-1KA15 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m

Specifications

3RV1011-1KA15 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

What it is and what it does

The Siemens SIRIUS 3RV1011-1KA15 is a motor-protective circuit breaker with a CLASS 10 trip characteristic. It mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 60715, in any orientation, so it fits into a standard motor control center or panel without special bracketry.

Breaking capacity and motor rating

The interrupting rating hits 100 kA at 240 V, dropping to 13 kA at 400 V, 3 kA at 500 V, and 2 kA at 690 V — this tells you the maximum fault current the breaker can safely clear at each voltage level, which is the key figure for SCCR coordination in the panel. Motor full-load current rating is 2 hp at 230 V, which corresponds to roughly 12 A at 480 V and 12 A at 600 V — the breaker's thermal element is sized for that motor FLA range.

Panel integration and wiring

Dimensions: 45 mm wide × 90 mm tall × 75 mm deep, with 20 mm clearance required above and below, 9 mm at the sides, and zero forwards/backwards — this is the minimum free space around the breaker for heat dissipation and arc-fault containment. Main contact terminals accept 2× (0.5 to 1.5 mm²) or 2× (0.75 to 2.5 mm²) solid or stranded copper, terminated with M3 screws — standard for panel wiring up to 2.5 mm².

Frequently asked questions

What is the closest functional second-source for 3RV1011-1KA15?

The closest functional peer is 3RV1011-1HA10, which shares the same SIRIUS platform, DIN-rail footprint, and CLASS 10 trip class. The key difference to check is the thermal setting range and breaking capacity at your specific voltage — verify those against your motor FLA before substituting.

MPN