Siemens 3RV1011-1KA15 — Motor Protection Circuit Breakers (MPCB)

Siemens SIRIUS 3RV1011-1KA15 Circuit Breaker, CLASS 10, 100

MPN3RV1011-1KA15
Active

Siemens SIRIUS 3RV1011-1KA15 circuit breaker, CLASS 10 trip class, 100 kA breaking capacity at 240 V, 2 hp motor rating at 230 V, screw and snap-on mounting on 35 mm DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV1011-1KA15 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV1011-1KA15 — Electrical
ParameterValue
Rated operational current (Ie)12 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)9.25 W
Power loss, per pole (AC, hot)3.1 W
3RV1011-1KA15 — Protection & Tripping
ParameterValue
Overload release setting range9 ... 12.5 A
Instantaneous short-circuit trip current156 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)50 kA
Breaking capacity at 500 V (AC)3 kA
Breaking capacity at 690 V (AC)2 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V2 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV1011-1KA15 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0
3RV1011-1KA15 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
3RV1011-1KA15 — Mechanical
ParameterValue
Height90 mm
Width45 mm
Depth75 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV1011-1KA15 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV1011-1KA15 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

Breaking capacity and motor rating

The interrupting rating hits 100 kA at 240 V, dropping to 13 kA at 400 V, 3 kA at 500 V, and 2 kA at 690 V — this tells you the maximum fault current the breaker can safely clear at each voltage level, which is the key figure for SCCR coordination in the panel. Motor full-load current rating is 2 hp at 230 V, which corresponds to roughly 12 A at 480 V and 12 A at 600 V — the breaker's thermal element is sized for that motor FLA range.

Dimensions: 45 mm wide × 90 mm tall × 75 mm deep, with 20 mm clearance required above and below, 9 mm at the sides, and zero forwards/backwards — this is the minimum free space around the breaker for heat dissipation and arc-fault containment. Main contact terminals accept 2× (0.5 to 1.5 mm²) or 2× (0.75 to 2.5 mm²) solid or stranded copper, terminated with M3 screws — standard for panel wiring up to 2.5 mm².