Breaking capacity and fault clearing
This breaker carries a 100 kA rated short-circuit breaking capacity across the full voltage range: 240 V, 400 V, 500 V, and 690 V AC (–).
Depth is 96 mm, height 97 mm — check the gland plate clearance if the panel is shallow. No side or backward spacing required, so you can pack modules tight.
The main circuit accepts solid conductors: 2×(0.5…1.5 mm²) or 2×(0.75…2.5 mm²). Stranded: 2×(1…2.5 mm²) or 2×(2.5…6 mm²). AWG equivalent for the main contacts is 2×(14…10). The auxiliary switch is transverse design and the product extension auxiliary switch is available. Wire the load side to the motor contactor; the breaker's own auxiliary contacts can feed a PLC input for status feedback.
Substance prohibitance date of 01.05.2012 aligns with RoHS compliance — the part is free of restricted substances per EU Directive 2011/65/EU. Shock resistance rated at 25 g for 11 ms. Mounting position is any, giving flexibility in panel layout.