It carries a 0.32 A continuous current rating and trips CLASS 10, meaning it clears an overload before the motor windings reach their thermal limit under locked-rotor conditions.
Breaking capacity and voltage ceiling
Rated breaking capacity holds at 100 kA across the board — 240 V, 400 V, 500 V, and 690 V AC — so it handles high-fault utility feeds without cascading upstream.
Terminal wiring accepts solid or stranded conductors: 2x (1 to 2.5 mm²) and 2x (2.5 to 6 mm²) per pole, screw-type. That covers most motor feed cables up to 6 mm². Auxiliary switch can be added on the side; the breaker is prepared for it.
Shock rated at 25g for 11 ms. Front protection is IP20 — finger-safe but not washdown-rated. RoHS compliance date is 01.05.2012, and the lifecycle status is current, so this is an active catalog line, not a phase-out.