Skip to main content
Siemens 3RV1021-0DA15-ZW96 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1021-0DA15-ZW96 SIRIUS Motor Protection Circuit B

MPN3RV1021-0DA15-ZW96

Siemens SIRIUS 3RV1021-0DA15-ZW96 motor protection circuit breaker, 0.32 A continuous rated current, Class 10 trip class, 100 kA breaking capacity at 400 V AC, screw-type terminals, 45 x 97 x 96 mm.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV1021-0DA15-ZW96 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1021-0DA15-ZW96 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W
3RV1021-0DA15-ZW96 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Phase-failure detectionYes
Ground-fault detectionNo
3RV1021-0DA15-ZW96 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
3RV1021-0DA15-ZW96 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
3RV1021-0DA15-ZW96 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting positionany
3RV1021-0DA15-ZW96 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
3RV1021-0DA15-ZW96 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

Motor protection circuit breaker, 0.32 A, Class 10 — SIRIUS 3RV1021-0DA15-ZW96

No ground fault detection on this unit. The main contacts are rated for 100,000 mechanical operations typical. Auxiliary switch is present (transverse design), with zero auxiliary contacts for the main current circuit — the switch is integrated, not a separate block.

Mounting and panel integration — DIN rail, any position

Depth is 96 mm, width 45 mm, height 97 mm. Zero clearance needed at the sides or backwards. Front face is IP20 — touch-safe for panel interior, but not sealed against washdown or dust. Maximum operating altitude 2,000 m.

Termination and wiring — screw-type terminals

Solid conductor capacity: 2x (0.5... 1.5 mm²) and 2x (0.75... 2.5 mm²). Stranded: 2x (1... 2.5 mm²) and 2x (2.5... 6 mm²). Power dissipation at AC in hot operating state is 5.5 W. Auxiliary switch contacts rated: 1 A at 24 V, 0.5 A at 230 V, 0.15 A at 60 V. Rated insulation voltage 690 V.

Sourcing and lifecycle — currently in production

Frequently asked questions

Where can I buy 3RV1021-0DA15-ZW96 and how do I get a price?

This part is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

What is 3RV1021-0DA15-ZW96's continuous current rating?

The continuous current rated value is 0.32 A. Trip class is Class 10, meaning it will trip within 10 seconds at 7.2x rated current — suitable for standard induction motor starting profiles.

What breaking capacity does 3RV1021-0DA15-ZW96 have at 400 V?

100 kA at 400 V AC. Also 100 kA at 240 V, 500 V, and 690 V AC. That's a high interrupting rating for a compact DIN-rail breaker — it handles severe fault currents without needing upstream fuses in most panels.

What is the depth of 3RV1021-0DA15-ZW96?

Depth is 96 mm. Width 45 mm, height 97 mm. Zero clearance required at sides or back.

What wire sizes does the 3RV1021-0DA15-ZW96 accept?

Solid: 2x (0.5... 1.5 mm²) and 2x (0.75... 2.5 mm²). Stranded: 2x (1... 2.5 mm²) and 2x (2.5... 6 mm²). Screw-type terminals on the main current circuit.