Siemens 3RV1021-0DA15-ZW97 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1021-0DA15-ZW97 SIRIUS Motor Protection CB, 0.32

MPN3RV1021-0DA15-ZW97

Siemens SIRIUS motor protection circuit breaker, 3RV1021-0DA15-ZW97, 0.32 A continuous rated current, Class 10 trip, 100 kA breaking capacity at 400 V AC, screw terminals, snap-on 35 mm DIN rail.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1021-0DA15-ZW97 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker

Electrical

3RV1021-0DA15-ZW97 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W

Protection & Tripping

3RV1021-0DA15-ZW97 — Protection & Tripping
ParameterValue
Overload release setting range0.22 ... 0.32 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV1021-0DA15-ZW97 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0

Connections

3RV1021-0DA15-ZW97 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (14 ... 10)

Mechanical

3RV1021-0DA15-ZW97 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany

Environmental

3RV1021-0DA15-ZW97 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m

Specifications

3RV1021-0DA15-ZW97 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

What it is and what it does

The Siemens 3RV1021-0DA15-ZW97 is a SIRIUS motor protection circuit breaker designed for motor protection, with screw-type terminals for the main and auxiliary circuits. Continuous rated current is 0.32 A with Trip Class CLASS 10. The breaking capacity is 100 kA at 400 V AC, so it safely interrupts fault currents up to that level without cascading upstream — critical for high-fault panels where a lower-rated device would require a current-limiting upstream breaker.

Mounting and integration

Mounts via screw and snap-on onto 35 mm standard mounting rail per DIN EN 50022, in any mounting position. Dimensions are 45 mm wide, 97 mm high, 96 mm deep — fits a standard 45 mm module slot on the DIN rail with zero clearance required at the back or sides. IP20 protection on the front means it is finger-safe for panel installation but not rated for washdown environments. Wire sizes: solid conductors accept 2x (0.5…1.5 mm²) and 2x (0.75…2.5 mm²); stranded accept 2x (1…2.5 mm²) and 2x (2.5…6 mm²); AWG for main contacts is 2x (14…10).

Environmental and compliance

Operating temperature range is -20 to +60 °C; storage and transport range is -50 to +80 °C. Shock resistance rated at 25g for 11 ms. Substance prohibitance (RoHS compliance) dated 01.05.2012.

Frequently asked questions

Does 3RV1021-0DA15-ZW97 have phase failure detection?

Yes, it includes phase failure detection; it does not include ground fault detection.

MPN