DIN rail fit and wiring
The 45 mm wide body accepts solid or stranded conductors: 2x (1... 2.5 mm²) and 2x (2.5... 6 mm²) per terminal. Depth is 96 mm, height 97 mm — fits standard distribution boards without crowding the gland plate.
Breaking capacity and duty cycle
Rated short-circuit breaking capacity holds at 100 kA across the voltage range: 240 V, 400 V, 500 V, and 690 V AC. That's consistent fault clearance regardless of supply voltage within the rated range. Maximum operating frequency is 15 operations per hour at AC-3 duty — fine for motor starting, not for rapid cycling. Power dissipation is 5.5 W hot, 1.8 W per pole, so derating in a sealed enclosure is worth checking if you're packing multiple units.