Skip to main content
Siemens 3RV1021-0EA10-ZX95 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1021-0EA10-ZX95 SIRIUS Motor Protection Circuit B

MPN3RV1021-0EA10-ZX95

Siemens SIRIUS motor protection circuit breaker, 0.4 A, Class 10 trip, 100 kA breaking capacity at 400 V, screw terminals, DIN-rail mount, 3RV1021-0EA10-ZX95.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1021-0EA10-ZX95 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker

Electrical

3RV1021-0EA10-ZX95 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W

Protection & Tripping

3RV1021-0EA10-ZX95 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Phase-failure detectionYes
Ground-fault detectionNo

Endurance & Switching

3RV1021-0EA10-ZX95 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h

Connections

3RV1021-0EA10-ZX95 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)

Mechanical

3RV1021-0EA10-ZX95 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting positionany

Environmental

3RV1021-0EA10-ZX95 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C

Specifications

3RV1021-0EA10-ZX95 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

The Siemens SIRIUS 3RV1021-0EA10-ZX95 is a motor-protection circuit breaker rated for 0.4 A continuous current with a Class 10 trip characteristic, designed to protect low-current motor loads in control panels. Its 100 kA breaking capacity at 400 V AC means it can safely interrupt high fault currents without cascading upstream — critical for selectivity coordination in a distribution panel. The unit mounts via screw or snap-on onto 35 mm DIN rail per EN 50022, fitting standard panel layouts with a 45 mm width and 97 mm height.

Key Ratings and What They Mean for Fit

The 0.4 A continuous rating governs the motor FLA it protects — size this breaker to match the motor's nameplate full-load amps, not the supply capacity. The Class 10 trip provides fast overload response for standard induction motors, clearing within 10 seconds at 600% of set current. Rated operational voltage reaches 690 V AC, with the switching capacity holding at 100 kA across the 240 V to 690 V range (–). That SCCR headroom simplifies panel coordination — the breaker can be placed downstream of a transformer or main switch without derating. Phase failure detection is built in, so the breaker will trip on loss of one phase — a common failure mode in motor circuits that single-element overloads miss. Screw-type terminals on the main circuit accept solid or stranded conductors: 2x 1–2.5 mm² or 2x 2.5–6 mm² per pole. The AWG equivalent is 2x 14–10 AWG. No auxiliary contacts are included, but the design accepts add-on blocks if needed.

Integration and Deployment

Snap-on mounting onto 35 mm DIN rail per EN 50022 with zero clearance required at the sides or rear — the 45 mm width fits a standard 8-module spacing. Ambient operating range is -20 to +60 °C; storage and transport range is -50 to +80 °C. Mounting position is any orientation. Shock resistance is rated at 25 g for 11 ms, suitable for industrial machinery and panel-mounted applications subject to vibration. IP20 finger-safe protection on the front — adequate for enclosed panels; no washdown rating, so keep this inside a cabinet.

Lifecycle and Sourcing

The SIRIUS 3RV family is a well-established platform; no direct official successor has been published for this order code.

Frequently asked questions

Where can I buy 3RV1021-0EA10-ZX95 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

What is the closest functional alternative to 3RV1021-0EA10-ZX95?

The 3RV1011-0GA10 is a similar SIRIUS motor-protection breaker but carries a different continuous current rating and trip class — verify your motor FLA and coordination requirements before substituting, as the 3RV1021-0EA10-ZX95 is sized for 0.4 A with Class 10 trip.

What is the depth of 3RV1021-0EA10-ZX95?

The depth is 96 mm, which fits standard 100 mm deep enclosures with clearance for wiring.

What conductor sizes does 3RV1021-0EA10-ZX95 accept?

The screw terminals accept 2x 1–2.5 mm² or 2x 2.5–6 mm² solid or stranded conductors, equivalent to 2x 14–10 AWG.

Will 3RV1021-0EA10-ZX95 drop into a panel specified around 3RV1011-0GA10?

The 45 mm width and DIN-rail mounting are identical across the 3RV1 series, so physical fit is the same. However, the 0.4 A rating and Class 10 trip differ — verify the motor protection settings match before swapping.

MPN