Specifications

3RV1021-0EA15-ZX95 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1021-0EA15-ZX95 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W
3RV1021-0EA15-ZX95 — Protection & Tripping
ParameterValue
Overload release setting range0.28 ... 0.4 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV1021-0EA15-ZX95 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0
3RV1021-0EA15-ZX95 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (14 ... 10)
3RV1021-0EA15-ZX95 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany
3RV1021-0EA15-ZX95 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m
3RV1021-0EA15-ZX95 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

The Siemens 3RV1021-0EA15-ZX95 is a SIRIUS motor protection circuit breaker rated for 0.4 A continuous current with a 100 kA breaking capacity at 400 V AC — enough to handle high-fault utility feeds without upstream fuses. It's designed for motor protection, includes phase failure detection, and trips on Class 10 overload curves, so it matches standard IEC motor starting profiles.

At 45 mm wide, it fits a standard single-module slot in a panel. Screw terminals on both main and auxiliary circuits — solid wire 2x (0.5... 1.5 mm²) or 2x (0.75... 2.5 mm²), stranded 2x (1... 2.5 mm²) or 2x (2.5... 6 mm²).

The 0.4 A continuous rating sets the motor full-load current this breaker protects — pair it with a motor nameplated at or below that value. The 100 kA breaking capacity holds across 240 V, 400 V, 500 V, and 690 V, so it's suitable for installations with high available fault current without needing a current-limiting upstream device.

Frequently asked questions

Where can I buy 3RV1021-0EA15-ZX95?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3RV1021-0EA15-ZX95?

It carries a 100 kA breaking capacity at 240 V, 400 V, 500 V, and 690 V AC — so it can interrupt high-fault currents without upstream fuses in most industrial panels.

Does 3RV1021-0EA15-ZX95 have phase failure protection?

Yes, phase failure detection is included — it will trip if one phase is lost, preventing motor single-phasing damage.

MPN