SIRIUS 3RV1021-0FA15-ZW98 — motor protection breaker, 0.5 A, CLASS 10
It carries a continuous current rating of 0.5 A and a CLASS 10 trip characteristic, meaning it disconnects within 10 seconds at 7.2× rated current — fast enough to protect standard induction motors during locked-rotor conditions without nuisance tripping on normal starts. The unit also includes phase failure detection, so a lost phase on the line side will trip the breaker before the motor single-phases.
Any mounting position is allowed. Terminals accept solid wire 2x (0.5...1.5 mm²) and 2x (0.75...2.5 mm²), or stranded 2x (1...2.5 mm²) and 2x (2.5...6 mm²).