3RV1021-0FA15-ZW98 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1021-0FA15-ZW98 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W
3RV1021-0FA15-ZW98 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Phase-failure detectionYes
Ground-fault detectionNo
3RV1021-0FA15-ZW98 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
3RV1021-0FA15-ZW98 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
3RV1021-0FA15-ZW98 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting positionany
3RV1021-0FA15-ZW98 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
3RV1021-0FA15-ZW98 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

SIRIUS 3RV1021-0FA15-ZW98 — motor protection breaker, 0.5 A, CLASS 10

It carries a continuous current rating of 0.5 A and a CLASS 10 trip characteristic, meaning it disconnects within 10 seconds at 7.2× rated current — fast enough to protect standard induction motors during locked-rotor conditions without nuisance tripping on normal starts. The unit also includes phase failure detection, so a lost phase on the line side will trip the breaker before the motor single-phases.

Any mounting position is allowed. Terminals accept solid wire 2x (0.5...1.5 mm²) and 2x (0.75...2.5 mm²), or stranded 2x (1...2.5 mm²) and 2x (2.5...6 mm²).

Frequently asked questions

Where can I buy 3RV1021-0FA15-ZW98 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is 3RV1021-0FA15-ZW98's listed depth?

Depth is 96 mm, with a width of 45 mm and height of 97 mm.

What wire sizes does the 3RV1021-0FA15-ZW98 accept?

Solid wire: 2x (0.5...1.5 mm²) and 2x (0.75...2.5 mm²). Stranded wire: 2x (1...2.5 mm²) and 2x (2.5...6 mm²). Main circuit uses screw-type terminals.

Will 3RV1021-0FA15-ZW98 drop into a panel specified around 3RV1011-0GA10?

Both are SIRIUS motor protection breakers on the same 45 mm DIN-rail footprint, so mechanical fit is the same. The 3RV1021-0FA15-ZW98 is a 0.5 A CLASS 10 device with 100 kA SCCR at 400 V; the 3RV1011-0GA10 is a different current rating and trip class. Verify the motor FLA and trip class match before substituting.