Ratings and so-what
The 3RV1021-0FA15-ZX95: Rated 0.5 A continuous, this breaker protects a motor drawing up to 0.12 kW at 400 V AC-3. Breaking capacity is 100 kA at 240 V, 400 V, 500 V, and 690 V AC. That covers most industrial fault-current scenarios up to the rated voltage; no need for upstream current-limiting fuses in a panel with sufficient SCCR. Any mounting position is allowed. Shock resistance is 25g for 11 ms. Front protection is IP20.