It interrupts faults up to 100 kA at 400 V AC, covering the full range from 240 V through 690 V at the same 100 kA rating.
Mounting position is any orientation, so it works in horizontal or vertical bus layouts. The IP20 front face keeps fingers out of live terminals inside the panel.
Main and auxiliary/control circuits both use screw-type terminals. Solid and stranded conductors accept 2x (1 to 2.5 mm²) or 2x (2.5 to 6 mm²) per clamp. AWG equivalents are 2x (14 to 10) for the main contacts. No backwards clearance needed at the terminals — 0 mm rear clearance means it can sit flush against the back panel or a busbar.
Electrical performance
Power dissipation in hot operating state is 5.5 W total, 1.8 W per pole. Maximum operating frequency under AC-3 duty is 15 operations per hour. The 0.18 kW rating at 400 V gives a direct motor sizing reference for a standard 4-pole induction motor.