Skip to main content
Siemens 3RV1021-1AA10-ZW95 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1021-1AA10-ZW95 SIRIUS Motor Protection Circuit B

MPN3RV1021-1AA10-ZW95

Siemens SIRIUS motor protection circuit breaker, 3RV1021-1AA10-ZW95, 1.6 A, CLASS 10, 100 kA breaking capacity at 400 V, screw terminals, 45 mm width.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RV1021-1AA10-ZW95 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1021-1AA10-ZW95 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W
3RV1021-1AA10-ZW95 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Phase-failure detectionYes
Ground-fault detectionNo
3RV1021-1AA10-ZW95 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
3RV1021-1AA10-ZW95 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
3RV1021-1AA10-ZW95 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting positionany
3RV1021-1AA10-ZW95 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
3RV1021-1AA10-ZW95 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

What this breaker does on the line

The 690 V rated insulation voltage matches the upper end of common industrial supply systems. Power dissipation runs 7.25 W total in hot operating state, or 2.4 W per pole — a consideration for dense DIN-rail enclosures where heat buildup can derate adjacent devices.

Screw-type terminals on the main circuit accept solid or stranded conductors: two conductors per clamp, 1 to 2.5 mm² or 2.5 to 6 mm², AWG 14–10. The auxiliary switch option is present on this variant, so you can wire a status contact back to the PLC without an add-on block. The 45 mm width (three module spaces) is typical for this current class. Shock rated at 25 g for 11 ms, so it survives shipping and panel vibration in industrial environments.

Frequently asked questions

Where can I buy 3RV1021-1AA10-ZW95 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3RV1021-1AA10-ZW95?

Rated breaking capacity is 100 kA at 240 V, 400 V, 500 V, and 690 V AC — consistent across the full voltage range, so it handles high-fault panels without derating.

What is the depth of 3RV1021-1AA10-ZW95?

The depth is 96 mm, with 0 mm clearance required at the side and rear for mounting on DIN rail.

What wire sizes does the 3RV1021-1AA10-ZW95 accept?

Screw terminals accept solid or stranded conductors: two conductors per clamp in ranges 1 to 2.5 mm² and 2.5 to 6 mm², or AWG 14–10.

MPN
3RV1021-1AA10-ZW95