Skip to main content
Siemens 3RV1021-1AA10-ZW97 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1021-1AA10-ZW97 SIRIUS Motor Protection Circuit B

MPN3RV1021-1AA10-ZW97

Siemens SIRIUS 3RV1021-1AA10-ZW97 motor protection circuit breaker, 1.6 A continuous current, Class 10 trip, 100 kA breaking capacity at 400 V AC, screw terminals, 45 mm wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RV1021-1AA10-ZW97 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1021-1AA10-ZW97 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W
3RV1021-1AA10-ZW97 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Phase-failure detectionYes
Ground-fault detectionNo
3RV1021-1AA10-ZW97 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
3RV1021-1AA10-ZW97 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
3RV1021-1AA10-ZW97 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting positionany
3RV1021-1AA10-ZW97 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
3RV1021-1AA10-ZW97 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

Motor protection circuit breaker for the line

The Class 10 trip curve matches standard motor start profiles; it holds through the inrush and still clears a locked-rotor fast enough to keep the winding from cooking.

Rated continuous current is 1.6 A — that's the full-load current it's sized for. The 0.55 kW rating at 400 V tells you the motor it protects. This one doesn't, so it's a good fit for panels with high available fault current.

Depth is 96 mm, so it clears most shallow enclosures. Screw terminals accept 2x (1... 2.5 mm²) solid or stranded, or 2x (2.5... 6 mm²) — that is the range for the main circuit wiring. IP20 on the front; no washdown rating, so keep it inside the panel.

No EOL notice or successor has been issued.

Frequently asked questions

What is the breaking capacity of 3RV1021-1AA10-ZW97?

It is rated 100 kA at 240 V, 400 V, 500 V, and 690 V AC — the same high interrupting rating across the voltage range.

Where can I buy 3RV1021-1AA10-ZW97?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the trip class of 3RV1021-1AA10-ZW97?

It is Class 10, which means it trips within 10 seconds at a locked-rotor condition — standard for general-purpose motor starting.

Does 3RV1021-1AA10-ZW97 fit on a DIN rail?

Yes, it mounts on a 35 mm DIN rail per EN 50022, with screw and snap-on mounting. The 45 mm width fits standard modular panels.

MPN
3RV1021-1AA10-ZW97