Skip to main content
Siemens 3RV1021-1AA10-ZW98 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1021-1AA10-ZW98 SIRIUS Motor Protection Circuit B

MPN3RV1021-1AA10-ZW98

Siemens SIRIUS 3RV1021-1AA10-ZW98, motor protection circuit breaker, 1.6 A, CLASS 10, 100 kA at 400 V AC, screw terminals, IP20 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RV1021-1AA10-ZW98 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1021-1AA10-ZW98 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W
3RV1021-1AA10-ZW98 — Protection & Tripping
ParameterValue
Overload release setting range1.1 ... 1.6 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV1021-1AA10-ZW98 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0
3RV1021-1AA10-ZW98 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
Conductor range, AWG (main contacts)2x (14 ... 10)
3RV1021-1AA10-ZW98 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany
3RV1021-1AA10-ZW98 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m
3RV1021-1AA10-ZW98 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

Motor protection circuit breaker for 1.6 A loads

The Siemens SIRIUS 3RV1021-1AA10-ZW98 is a 3-pole motor protection circuit breaker rated for a continuous current of 1.6 A, with a CLASS 10 trip characteristic — meaning it disconnects within 10 seconds at 7.2× the thermal setting, sized to protect standard induction motors during locked-rotor starts without nuisance tripping on normal acceleration. Breaking capacity hits 100 kA across the full voltage range — 240 V, 400 V, 500 V, and 690 V AC — so it safely interrupts fault currents up to that level without cascading upstream, even on high-SCCR panels. Rated motor power is 0.55 kW at 400 V AC-3 duty, which covers small pump, fan, and conveyor drives in a 400 V line.

DIN-rail mounting and wiring

Depth is 96 mm, height 97 mm, with 0 mm clearance required at the back and sides — it sits flush against the backplane, simplifying enclosure layout. Main and auxiliary circuits use screw-type terminals accepting 2x (1 to 2.5 mm²) solid or stranded, or 2x (2.5 to 6 mm²) — the larger cross-section handles the full 1.6 A load without derating, while the smaller pair accommodates daisy-chained control wiring.

Shock resistance is 25 g for 11 ms, and surge voltage withstand is 6 000 V — figures that qualify it for industrial environments with frequent switching transients.

Frequently asked questions

How do I get current pricing and availability for 3RV1021-1AA10-ZW98?

Submit an RFQ through this listing; availability and current pricing are confirmed at quote time through independent distribution channels.

What is 3RV1021-1AA10-ZW98's listed depth?

The depth is 96 mm, with 0 mm clearance required at the back and sides for flush mounting against the enclosure backplane.

What wire sizes does the 3RV1021-1AA10-ZW98 accept?

Screw terminals accept 2x (1 to 2.5 mm²) or 2x (2.5 to 6 mm²) for both solid and stranded conductors on main and auxiliary circuits.

What compliance documentation does this SIRIUS breaker provide?

RoHS compliance is documented with a substance prohibitance date of 01.05.2012; the part also carries IP20 front protection and is designed to IEC/EN 60947 standards for motor protection.

MPN
3RV1021-1AA10-ZW98