It carries a continuous current rating of 1.6 A and a trip class of CLASS 10, meaning it will trip within 10 seconds at 7.2× rated current — fast enough to protect standard induction motors during locked-rotor conditions without nuisance tripping on normal starts. Breaking capacity is 100 kA across the board at 240 V, 400 V, 500 V, and 690 V AC, so it can be applied on high-fault-current panels without worrying about series rating coordination downstream. This breaker catches that condition.
Any mounting position is permitted. Zero clearance required at the sides or rear for heat dissipation. Main circuit terminals accept solid conductors 2×(0.5…1.5 mm²) and 2×(0.75…2.5 mm²), or stranded 2×(1…2.5 mm²) and 2×(2.5…6 mm²). AWG equivalents for the main contacts are 2×(14…10). Auxiliary and control circuits use screw terminals as well.
RoHS compliance is documented with a substance prohibition date of 01.05.2012, indicating it meets the EU RoHS directive effective from that date.
Shock resistance is 25 g for 11 ms, so it holds calibration and mechanical integrity under moderate vibration and impact in industrial environments. Maximum operating frequency in AC-3 duty is 15 operations per hour, which limits its use in high-cycling applications like rapid reversing or jogging.