The Siemens 3RV1021-1BA10 is a SIRIUS motor protection circuit breaker rated for 2 A continuous current with a Class 10 trip characteristic, sized for a 0.75 kW motor at 400 V.
Any mounting position is allowed.
The 2 A continuous rating sets the motor full-load current it protects; the Class 10 trip curve means it will disconnect within 10 seconds at 7.2× rated current, matching standard induction motor starting profiles. At 690 V the breaking capacity drops to 8 kA, so verify the line voltage if used on 690 V systems. Power dissipation is 7.25 W hot (2.4 W per pole), which matters for thermal management in a dense panel. Shock resistance of 25g / 11 ms covers most industrial vibration environments.
Terminal and Wiring
Screw-type terminals for main and auxiliary circuits accept solid or stranded conductors: 2x (1 … 2.5 mm²) and 2x (2.5 … 6 mm²). For AWG, 2x (14 … 10). Finely stranded wire with core end processing is also supported. The auxiliary switch extension is available as an add-on, so the breaker can signal its state to a PLC or status light.