Skip to main content
Siemens 3RV1021-1BA10-ZW98 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1021-1BA10-ZW98 SIRIUS Motor Protection Circuit B

MPN3RV1021-1BA10-ZW98

Siemens SIRIUS motor protection circuit breaker, 3RV1021-1BA10-ZW98, 2 A continuous, CLASS 10 trip, 100 kA breaking at 400 V AC, screw terminals, IP20 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV1021-1BA10-ZW98 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1021-1BA10-ZW98 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W
3RV1021-1BA10-ZW98 — Protection & Tripping
ParameterValue
Overload release setting range1.4 ... 2 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)8 kA
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV1021-1BA10-ZW98 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0
3RV1021-1BA10-ZW98 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
Conductor range, AWG (main contacts)2x (14 ... 10)
3RV1021-1BA10-ZW98 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany
3RV1021-1BA10-ZW98 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m
3RV1021-1BA10-ZW98 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

The Siemens 3RV1021-1BA10-ZW98 is a SIRIUS motor protection circuit breaker rated for 2 A continuous current with a CLASS 10 trip characteristic, meaning it disconnects within 10 seconds at 7.2× the set current — fast enough to protect standard induction motors during a locked-rotor event. The unit also accepts an auxiliary switch (product extension auxiliary switch: Yes) for remote status feedback.

Terminals accept solid and stranded conductors: 2x (1 … 2.5 mm²) and 2x (2.5 … 6 mm²), with AWG equivalents 2x (14 … 10). Depth is 96 mm, width 45 mm, height 97 mm — zero clearance needed at the back or sides for heat dissipation.

Rated for a 0.75 kW motor at 400 V AC-3 duty, with a maximum operating frequency of 15 switching cycles per hour. Power dissipation at rated current is 7.25 W total (2.4 W per pole). Surge voltage resistance is 6 000 V. Storage and transport temperature range is -50 … +80 °C; operating range is -20 … +60 °C. Shock resistance: 25g / 11 ms. Compliance: RoHS substance prohibition date is 01 May 2012. Ground fault detection is not included — this is a standard motor-protective breaker, not a ground-fault device.

Frequently asked questions

What is 3RV1021-1BA10-ZW98's listed depth (96 mm) on this component line?

The depth is 96 mm, with zero clearance required at the back or sides for heat dissipation.

What is 3RV1021-1BA10-ZW98's listed solid (2x (1 … 2.5 mm²), 2x (2.5 … 6 mm²)) on this component line?

The solid conductor capacity is 2x (1 … 2.5 mm²) and 2x (2.5 … 6 mm²), with AWG equivalents 2x (14 … 10). Stranded and finely stranded with core end processing share the same ranges.

Will 3RV1021-1BA10-ZW98 drop into a panel that was specified around 3RV1011-0GA10 without rewiring?

Yes, the 3RV1021-1BA10-ZW98 shares the same 45 mm width, DIN-rail mounting, and screw-terminal layout as the 3RV1011-0GA10. The wire size ranges are identical (solid/stranded up to 6 mm²). No panel modification or re-termination is needed — just set the current dial to 2 A and confirm the motor FLA matches.

MPN