Skip to main content
Siemens 3RV1021-1DA10-ZW96 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1021-1DA10-ZW96 SIRIUS Motor Circuit Breaker, 3.2

MPN3RV1021-1DA10-ZW96

Siemens SIRIUS motor protection circuit breaker, 3RV1021-1DA10-ZW96, 3.2 A continuous, 100 kA breaking at 400 V, Class 10 trip, screw terminals, 45 mm wide.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV1021-1DA10-ZW96 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1021-1DA10-ZW96 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W
3RV1021-1DA10-ZW96 — Protection & Tripping
ParameterValue
Overload release setting range2.2 ... 3.2 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)8 kA
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV1021-1DA10-ZW96 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0
3RV1021-1DA10-ZW96 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
Conductor range, AWG (main contacts)2x (14 ... 10)
3RV1021-1DA10-ZW96 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany
3RV1021-1DA10-ZW96 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m
3RV1021-1DA10-ZW96 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

The Siemens 3RV1021-1DA10-ZW96 is a SIRIUS motor protection circuit breaker rated for 3.2 A continuous current with a 100 kA breaking capacity at 400 V AC — enough to handle high-fault utility feeds without cascading upstream.

Trip class and breaking capacity

Class 10 trip means the breaker opens within 10 seconds at a locked-rotor current — standard for motor protection on pumps, fans, and compressors where the inrush is high but sustained overload damages windings. The 100 kA breaking capacity at 400 V is the same across 240 V and 500 V; at 690 V it drops to 8 kA. That 100 kA rating lets you place this breaker downstream of a transformer or bus without worrying about fault current coordination.

Accepts 2x (1 to 2.5 mm²) solid or stranded, or 2x (2.5 to 6 mm²).

MPN
3RV1021-1DA10-ZW96