Skip to main content
Siemens 3RV1021-1DA15-ZW96 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1021-1DA15-ZW96 SIRIUS Motor Protection Circuit B

MPN3RV1021-1DA15-ZW96

Siemens SIRIUS motor protection circuit breaker, 3RV1021-1DA15-ZW96, 3.2 A continuous current, CLASS 10 trip, 100 kA breaking capacity at 400 V AC, screw terminals, snap-on 35 mm DIN rail.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1021-1DA15-ZW96 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker

Electrical

3RV1021-1DA15-ZW96 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W

Protection & Tripping

3RV1021-1DA15-ZW96 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)8 kA
Phase-failure detectionYes
Ground-fault detectionNo

Endurance & Switching

3RV1021-1DA15-ZW96 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h

Connections

3RV1021-1DA15-ZW96 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)

Mechanical

3RV1021-1DA15-ZW96 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting positionany

Environmental

3RV1021-1DA15-ZW96 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C

Specifications

3RV1021-1DA15-ZW96 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

Motor protection circuit breaker, 3.2 A, CLASS 10, 100 kA

The Siemens SIRIUS 3RV1021-1DA15-ZW96 is a motor protection circuit breaker rated for a continuous current of 3.2 A with a CLASS 10 trip characteristic, meaning it will trip within 10 seconds at 7.2× the set current — fast enough to protect standard induction motors during a stall or locked-rotor event without nuisance tripping on normal starting inrush. Breaking capacity is 100 kA at 240 V, 400 V, and 500 V AC, dropping to 8 kA at 690 V AC. That 100 kA rating at common distribution voltages (400 V) means this breaker can be installed downstream of a high-capacity transformer without needing a current-limiting upstream device — it clears a bolted fault up to 100 kA on its own. Mounts via screw and snap-on onto a 35 mm standard mounting rail per DIN EN 50022. The IP20 rating on the front means it's protected against finger contact but not against water ingress — standard for enclosed panel installation.

Integration and wiring

Screw-type terminals for the main current circuit accept solid conductors: 2×(0.5…1.5 mm²) and 2×(0.75…2.5 mm²). Stranded conductors: 2×(1…2.5 mm²) and 2×(2.5…6 mm²). The auxiliary switch is transverse design; the breaker includes an auxiliary switch (yes) but no auxiliary contacts for the main circuit (0). Phase failure detection is built in — if one phase drops out, the breaker trips, preventing single-phasing damage to the motor. No ground-fault detection. Trip class CLASS 10 matches most standard motor starting profiles. Operating temperature range -20 to +60 °C; storage and transport -50 to +80 °C. Shock rated at 25g / 11 ms. Mounting position any. Dimensions: 45 mm wide, 97 mm high, 96 mm deep — fits a standard 45 mm modular device footprint on DIN rail.

Frequently asked questions

What is the breaking capacity of 3RV1021-1DA15-ZW96 at 400 V?

100 kA at 400 V AC, which is the same rating at 240 V and 500 V AC. At 690 V AC it drops to 8 kA.

Where can I buy 3RV1021-1DA15-ZW96?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the trip class of this breaker?

CLASS 10 — it will trip within 10 seconds at 7.2× the set current, suitable for standard motor starting.

Does 3RV1021-1DA15-ZW96 include phase failure detection?

Yes, phase failure detection is built in. It does not include ground-fault detection.

MPN