Skip to main content
Siemens 3RV1021-1EA10-0FJ0-ZX95 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1021-1EA10-0FJ0-ZX95 SIRIUS Motor Protection CB,

MPN3RV1021-1EA10-0FJ0-ZX95

Siemens SIRIUS motor protection circuit breaker, 3RV1021-1EA10-0FJ0-ZX95, 4 A rated continuous current, Class 10 trip, 100 kA breaking capacity at 400 V AC, screw terminals, for 35 mm DIN rail.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV1021-1EA10-0FJ0-ZX95 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker

Electrical

3RV1021-1EA10-0FJ0-ZX95 — Electrical
ParameterValue
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3

Protection & Tripping

3RV1021-1EA10-0FJ0-ZX95 — Protection & Tripping
ParameterValue
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)6 kA
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV1021-1EA10-0FJ0-ZX95 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0

Connections

3RV1021-1EA10-0FJ0-ZX95 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementfront side

Mechanical

3RV1021-1EA10-0FJ0-ZX95 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting positionany

Environmental

3RV1021-1EA10-0FJ0-ZX95 — Environmental
ParameterValue
Max. installation altitude2 000 m

Specifications

3RV1021-1EA10-0FJ0-ZX95 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

SIRIUS 3RV1021-1EA10-0FJ0-ZX95 — Motor Protection Circuit Breaker, 4 A, Class 10

The Siemens SIRIUS 3RV1021-1EA10-0FJ0-ZX95 is a three-pole motor protection circuit breaker with a thermomagnetic overcurrent and short-circuit release, rated for a continuous current of 4 A and a motor power of 1.5 kW at 400 V. Its Class 10 trip characteristic means it will trip within 10 seconds at 7.2× the thermal setting — the standard for protecting standard induction motors during start-up, where the inrush current decays before the trip curve crosses. Breaking capacity is 100 kA at 240 V, 400 V, and 500 V AC, dropping to 6 kA at 690 V AC — the high 100 kA figure at common distribution voltages (400 V) means this breaker can be used in high-fault-current panels without needing a current-limiting upstream device, simplifying selectivity coordination. Mounts via screw or snap-on onto 35 mm standard rail per DIN EN 50022, in any position, with a 45 mm width that occupies one standard 45 mm module slot — panel layout is straightforward.

Integration Notes

Depth is 96 mm, height 97 mm — the 96 mm depth is within the standard 100 mm deep enclosure profile, so it clears most shallow gland plates without a spacer. Phase failure detection is built in, so the breaker will trip on loss of any one phase — important for preventing single-phasing damage on delta-connected motors. No ground-fault detection on this variant; if GF is required, specify the -Z suffix options or an external module. Screw terminals on both main and auxiliary circuits; main terminals accept 2×(1…2.5 mm²) or 2×(2.5…6 mm²) solid/stranded — double-ferrule terminations are fine. The auxiliary switch option is available but this specific order code ships without auxiliary contacts (0 CO,). Rated operational voltage is 690 V AC, with an AC-3 motor switching rating of 4 A at 400 V and a maximum operating frequency of 15 operations per hour — sized for occasional motor starts, not high-duty cycling.

Frequently asked questions

What is the breaking capacity of this breaker at 400 V?

100 kA at 400 V AC, which is the same rating as at 240 V and 500 V; at 690 V it drops to 6 kA.

Where can I buy 3RV1021-1EA10-0FJ0-ZX95 and how is it quoted?

It is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What compliance documentation does this part carry?

As a Siemens SIRIUS product, it carries CE marking for the European market and is designed to IEC/EN 60947-2 and 60947-4-1 standards. RoHS and REACH declarations are available from Siemens on request. UL/CSA listings are typical for the SIRIUS family but should be confirmed against the specific order code for the target jurisdiction.

MPN