It carries a continuous current rating of 5 A and a trip class of CLASS 10, meaning it will trip within 10 seconds at 7.2× the set current, matching the thermal characteristic of standard induction motors during start-up. Rated for use up to 690 V, its breaking capacity is 100 kA at 240 V, 400 V, and 500 V AC, dropping to 6 kA at 690 V. At 400 V it is rated for 1.5 kW motor load, which is the typical sizing for a small pump or fan motor. It includes phase failure detection, which is critical for preventing single-phasing damage on three-phase motors. No ground fault detection is built in — that would require an add-on module or separate GFCI.
Accepts solid or stranded conductors: 2x (1 … 2.5 mm²) and 2x (2.5 … 6 mm²), or AWG 14–10. The dual-wire capacity per terminal is useful for daisy-chaining control power or looping through the line side. Dimensions: 96 mm deep, 97 mm tall. Zero clearance required at the back or sides, so it fits tight against the backplane or adjacent devices.
Shock rated at 25g / 11 ms. Surge voltage resistance at 6 000 V. Power dissipation is 7.25 W total in hot operating state (2.4 W per pole). RoHS compliance date is 01.05.2012.