Rated continuous current is 6.3 A, and the breaking capacity reaches 100 kA at 400 V AC (also 100 kA at 240 V and 500 V AC).
Where it goes and what it connects to
Panel depth allowance must accommodate the 96 mm body depth plus wiring bend radius. Main circuit terminals are screw-type, accepting solid or stranded conductors: 2×(1…2.5 mm²) and 2×(2.5…6 mm²), or AWG 14…10. Front face carries IP20 touch-safe protection; the busbar and live terminals behind the cover are not finger-safe until the cover is installed. No auxiliary contacts are included (0 auxiliary contacts), so any remote status signaling requires a separate auxiliary switch block snapped onto the side.
Environment and durability
The 25g / 11 ms shock resistance covers most industrial vibration and occasional mechanical impact during transport or panel door slam. Mechanical endurance of the main contacts is typically 100 000 operations; the maximum switching rate at AC-3 duty is 15 operations per hour. For a motor starting once every few minutes on a conveyor or pump, that rate is not a constraint — it only matters for high-cycle applications like rapid reversing or jogging.
